Necessity of center computer room monitoring
As the bridge between security center and outlets, the network computer room can guarantee that the data of lower outlets can circulate normally. Therefore, whether the work of center computer room is stable and reliable, has become the most important factor which can determine whether the communication of data dealing and lower outlets is smooth, so the computer room need be paid more attentions. As the based support of the equipment in center computer room, the smooth operation of network computer room is the premise and basis guaranteeing data operating of computer room, once there is any fault in computer room power environment, it will affect the operation of computer systems, and will threat the data transmission, storage and reliability of system operation, if the accident can not be handled in time, it may damage the hardware device of computer room, harm data security and cause serious consequence.
With the expansion of business, the computer room must be upgraded and expanded continually, in order to ensure the safety of system power supply, UPS power quantity also straights up subsequently. Because there are too many UPS brands and models, it is difficulty to manage. How to manage UPS easier?
.jpg)
Whether the quality of back-up battery is stable,it is the core for guaranteeing UPS can work normally, the fact shows more than 50% UPS fault is caused by battery fault, however, the special seal structure of UPS Vrla batteries resulted that we can not learn about the battery health status accurately. But, can we learn about the battery status accurately, in order to guarantee the UPS can operate normally?
.jpg)
With the increasing of load, heat dissipation has become the top killer of computer room, how to remote learn about temperature change in time?
Due to the lack of effective monitoring for computer room environment humidity, when the air humidity increases, the surface of components or dielectric material is extremely easy to form water film, and resulted in fly arc phenomenon, causing equipment fault; when the humidity is too low, that is to say, the air is drier, and the electrostatic voltage will be higher, it will affect the normal work of computer. Can we prevent the happen of the problem?
Computer room has configured all kinds of precision air conditioning in order to solve the heat dissipation, however, the precision air conditioning is lack of effective fault self-detect mechanism, when there is some fault, the air conditioning can not only solve the heat dissipation problem, but also may cause water leaking, fire……computer room accidents. Can we provide an effective monitoring mechanism to air conditioning?
Leaking problem has always been ignored by computer room management personnel, once slack phenomenon appears, if it can not be stopped timely and will bring immeasurable loss: short circuit, UPS and server, and other key equipment damage and even cause a fire. Can we find the leaking timely in order to avoid these problems?
Smoke detection is the last defense line for computer room fire warning system, numerous computer room fire accidents shows fire accident is more than 90%. Can we reduce or avoid the happening of the fire?
.jpg)
Due to a lack of effective monitoring of distribution system, uneven load distribution will result in power accidents, such as trip even short circuit. Can we avoid the happening of the trip and distribute load easily?
Traffic industry
Shanxi Fenyang highway toll power environment wireless monitoring
South China fast line UPS centralized monitoring
Hangzhou round highway UPS centralized monitoring
Shenzhen-Foshan highway toll UPS centralized monitoring
Shenzhen-Shantou highway toll monitoring
Xiamen bus UPS centralized monitoring
Guangzhou white cloud airport computer room environment monitoring
Xiamen BRT computer room UPS network centralized monitoring
Yongtaiwen, Zhejiang province high-speed computer room UPS network centralized monitoring
Yangmao highway toll computer room power environment monitoring
China Easten Airlines computer room power environment SMS monitoring
Shantou-Fenyang highway computer room power environment monitoring
Communication industry
Liaoyang branch business hall computer room UPS wireless centralized monitoring
Beijing telecommunication business outlets computer room UPS centralized monitoring
Beijing Great Wall broadband CO., LTD outlets UPS centralized monitoring (NEW)
Shanghai Zhongjin SmarTone district broadband network computer room and server shutoff protection
Wuhan, Hubei province Changqing garden district wire TV broadband network
Part of Dongguan branch of China mobile base station computer room
Zhengjiang province branch of China Unicom mobile communication base station
Government industry
Nanchang Public Security Bureau(PSB)center computer room overall environment monitoring
Yinchuan Ningdong power supply bureau
Fuzhou Public Security Bureau(PSB)UPS centralized monitoring project
Beijing National Tax Bureau branchs UPS network monitoring and server shutoff protection
Shenyang statistics computer room power environment wireless monitoring
Yunnan Judicature bureau computer room power environment SMS monitoring
Fujian weather bureau computer room power environment monitoring
The Tibet autonomous region communication administration computer room power system SMS monitoring
Education industry
Tianjin Medical university computer room UPS monitoring
Tianjin university computer room UPS monitoring
Xi'an industrial university computer room power system network monitoring
Power industry
Hangzhou Central Electricity Authority computer room power system monitoring
Radio and Television industry
Qinhuangdao Radio and Television computer room power system environment monitor
Changzhou broadcast station computer room UPS network centralized monitor
Changzhou Radio and Television studio centre power system network monitor
Financial industry
Shenzhen development bank Beijing branch computer room monitoring
Zhengjiang Industrial and Commercial Bank of China computer room power environment monitoring
Zhengjiang Industrial and Commercial Bank of China outlets UPS centralized monitoring
Zhuhai branch of agricultural bank of China outlets power environment centralized monitoring
Shanghai securities company data center power system SMS monitoring
Nanjing branch of bank of communications outlets power system network centralized monitoring
Shanghai Industrial and Commercial outlets UPS network centralized monitoring
Xiamen rural credit cooperative outlets UPS network centralized monitoring
Shanghai China Minsheng Banking CO., Ltd outlets UPS network centralized monitoring
Xiamen branch of China Merchants Bank outlets UPS network centralized monitoring
Dalian branch of Shanghai Pudong Development Bank outlets UPS centralized management
Enterprise industry
Shenzhen foxconn company computer room and server shutoff protection
Beijing capital airport terminal airlines building computer room UPS centralized monitoring (NEW)
Haerbin Seismological bureau and Tonghe seismological station information center power environment monitoring
Shanghai East Jiasheng shipping company computer room power environment SMS monitoring
Guangzhou Watsons outlets UPS centralized monitoring
System monitoring targets:
(1) Temperature and humidity remote centralized monitoring
Through field bus type data acquisition methods, collect computer room environment temperature and humidity data by using temperature and humidity sensors, combined with the IP network communication host, the system will report the site data to center data server, realize the unified centralized monitoring management for computer room environment temperature and humidity.
(2) Utility detection, UPS power monitor
Computer room utility supply is the precondition of the normal operation of computer room equipment. The utility power supply low voltage and high voltage is a large threat for computer room equipment. This system can online real-time monitor computer room utility supply status through intelligent current, voltage sensors, at the same time, it can also collect and monitor UPS running data parameters (including UPS input, output current, voltage, frequency, UPS temperature, battery voltage, etc) through UPS communication port by using UPS power monitoring adapter, these parameters can be transmitted to center server via Ethernet, so as to form large scope, no node limit network monitoring system. According to UPS protocol, the system can also carry on remote charging and discharging management for battery via monitoring center, in order to realize the intellectualized management of UPS.
In addition, our system can detect the fault status of lightning protection at all levels in utility power distribution cabinet, and know the open and close state of lightning protection, when there is any fault, the system can change it timely, in order to avoid the hidden danger in time.
(3) Fire control system remote centralized monitoring
Monitor the alarming status of fire control system in computer room, through the transmitted fire control alarming information of each computer room from fire control monitoring center host, administrator can real-time know the smoke alarming condition and fire control device running condition of computer room by graph
(4) Leaking monitoring system remote centralized monitoring
Install leaking testing lines in computer room where leaking may be happened, such as around air conditioning and next to the window, etc. administrator can real-time monitor the leaking status and alarm timely through monitoring leaking testing lines. Show and record the leaking status and leaking location sensed by leaking lines by simulation diagram, and real-time display the status of leaking controller. When air conditioning or other devices leak to the sensed lines, the monitoring system will send alarming. Recommend using line leaking sensor.
(5) Computer room air conditioning remote centralized monitoring
The good running state of communication equipment needs dry environment, in order to save energy, we need to intelligent control air conditioning, administrator can remote control air conditioning open/closed according to the temperature and humidity state in monitoring center system. The system can save electricity as much as possible in the temperature difference range which can guarantee the core equipment can operate normally.
(6) The centralized monitoring alarm management
Through internal LAN, build the whole monitoring center system through TCP/IP protocol. All monitoring data is centralized uploaded management via internal IP network. Monitoring center system only need a server installed IpPower 2009 computer room power environment monitoring center system and relevant database. The system can manage the whole computer room comprehensively. Monitoring center system can real-time monitor the temperature and humidity status, smoke fire alarming, leaking status, infrared intrusion-detection, entrance guard system, video system…… security and environment information, and utility power outage alarming, UPS and air conditioning state, etc; the system can also display each computer room environment state intuitively by configuration diagram; when the state mentioned above is abnormal, the system can inform the relevant personnel by mobile SMS, email…… timely, effectively and accurately, and handle the alarming information in time. The system can also be set to two backup copies, so as to satisfy the higher demand of users.
Center computer room functions
n Multi-area, multi-level, multi-user and multi-website powerful monitoring and management platform;
n 24-hour uninterrupted real-time monitor the running state of UPS and computer room comprehensive dynamic environment on line
n B/S architecture, easy to be used and managed;
n Show the real-time state of all kinds of dynamic monitoring device detailed and intuitively by data and graph
n Can display the monitoring interface by list, maps or room plane layout, according to the users’demands;
n Can realize remote operation and maintenance for UPS and computer room intelligent device, such as remote open/shutdown, etc;
n Mass data process ability, rapid monitoring response time;
n Powerful history records and statements management ability, strong specialist system management;
n Achieve utility statistics for the annual situation of device and all jurisdictional regions, through the statistics, users can see which month/season is blackout peak, the system can reflect the blackout situation of each season/month obviously by pie chart and bar chart, so that users and system administrators can learn about corresponding outage status easily, and prepare for power security next year
a) Can achieve utility blackout statistics for device and all jurisdictional regions, through the statistics, users can know which month/season is blackout peak and the proportion of blackout and normal utility;
b) The statements design from utility interrupted to battery low voltage is the lasted time statistics from utility interrupted to battery low voltage (that is to take the lasted time length as a coordinate point) the system can know battery status through the trend analysis; and can reflect by curve graph, the curve graph can reflect the working situation of each device;
c) Have corresponding statistics function for different faults;
d) Can realize the fault statistics and display by pie chart and bar chart, users can know the times and proportion of fault on device and all jurisdictional regions;
e) Realize various region fault statistic
f) Through the bar chart statistics, we can know the fault detailed times in various regions, and the system can reflect some fault happened state in some region. Users can make an accurate positioning for equipment repair through statistics.
n High-speed alarming response, diversified alarming ways: mobile SMS alarming, E-mail alarming, telephone and voice alarming, voice and broadcast alarming;
n System data copy and recovery function
n Large network database system, adopts MY SQL database, have powerful data storage and processing ability;
n Leading modular distributed program structure, powerful, flexible and convenient program expansion function;
n Support precise air conditioning device monitoring
n Support distribution cabinets real-time monitoring
n Support multi-brand, multi-type device centralized monitoring and management
n Can manage no more than 5000 comprehensive network nodes;
n Support 24-hour real-time monitoring and management for UPS
n Can manage different types of devices according to regional division
n Real-time detect the working state of monitored device, and send relevant alarming information through E-mail, SMS, etc.
n Can record history event about the device running status and history data of all the parameters
n Can check the history event and history data of the monitored device, users and system administrators can learn about the running status and working running trend of dynamic environment device, in order to guarantee the security and reliability of dynamic environment running intelligent device;
n Support Chinese/English display, operating interface is intuitive and friendly, easy to be used and installed;
n Provide server time-lapse shutdown the computer automatically,realize the function that the server can save the document automatically and the client can save the class document;
n Can realize remote operate and maintenance UPS, and can set timing operation, maintenance automatically, such as UPS battery discharging, etc;
n Optimized network communication mechanism, reduce the use of bandwidth effectively, promote the efficient, timely, the accuracy of alarming
l Support rate report (when the UPS data changes, sending data to background system automatically)
l Timely report (sending data to background timely) (exclusiveness 100%)
l Alarming report (when UPS alarming changes, sending data to background system automatically) (exclusiveness 100%)
l Active polling report (when the background system requests data, return relevant data to the background system)
|
Product Name
|
Content
|
|
|
1
|
Monitor Host and Background System
|
|
|
1.1
|
IP Power2009 power environment network monitor system software
|
WEB interface, B/S architecture, the software is stable and reliable, operation is simple and convenient, users can real time learn about the computer room running situation, and this software has message box alarm, voice alarm, email alarm, SMS alarm,etc
|
|
1.2
|
Mobile SMS Sending Module
|
SMS Sending Platform
|
|
1.3
|
Voice Dailing Alarm Host
|
Voice Dailing Alarm Platform
|
|
1.4
|
Local Sound-Light Alarm Device
|
Sound-light Alarm Platform
|
|
2
|
UPS Power Monitor System
|
|
|
2.1
|
Netmate II mini UPS Network Monitor Adapter (internal/3 phase)
|
Monitor 3 phase UPS, monitor 2 circuits temperature and humidity module, can be insected into Rackslot, each UPS need one device and need to provide accurate UPS model, this device can also expand one battery power inspection instrument。
|
|
2.2
|
Netmate II mini UPS Network Monitor Adapter (internal/1 phase)
|
Monitor 1 phase UPS, monitor 2 circuits temperature and humidity module, can be insected into Rackslot, each UPS need one device and need to provide accurate UPS model, this device can also expand one battery power inspection instrument。
|
|
3
|
Computer Room Environment Parameter Monitor System
|
|
|
3.1
|
Sitemate AE Computer Room Monitor Host
|
Able to realize 8 circuits temperature and humidity monitor, with 16 circuits dry-contact detect signal, can connect(smoke, door contact, infrared linkage module, etc), 2 circuits relay switch output, support air conditioning infrared control functon, etc
|
|
3.2
|
Intelligent High Precision Temperature and Humidity Detection Module
|
Special in computer room, high precision digital temperature and humidity sensor, temprature range is -55℃~+155℃, accuracy is ±0.5℃, Modbus RTU communication interface, full-duplex mode, strong anti-interference, stable and reliable.(one device/20~30㎡ )
|
|
3.2
|
Intelligent High Precision Temperature and Humidity Detection Module(With OLED Display)
|
Special in computer room, high precision digital temperature and humidity sensor, temprature range is -55℃~+155℃, accuracy is ±0.5℃, Modbus RTU communication interface, full-duplex mode, strong anti-interference, stable and reliable.(install one device/20~30㎡ )
|
|
3.3
|
Smoke Sensor
|
Monitor computer room smoke situation(install one device/20~30㎡ ), user can configure according to the real size of the computer room, one smoke sensor takes one switch quantity detection terminal.
|
|
3.4
|
Infrared Detector
|
Infrared double identification detector can judge whether the intrusion has been happened in related area by infrared microwave way, a infrared double identification detector takes up a switch quantity detection port
|
|
3.5
|
Fresh Air Switch State Transmitter
|
Used for detecting the switch state of air conditioning, fresh air, etc, it can be connected with Sitemate AE, only takes up one switch quantity detection port.
|
|
3.5
|
Common Air Conditoning Switch State Transmitter
|
Used for detecting the switch state of air conditioning, fresh air, etc, it can be connected with Sitemate AE, only takes up one switch quantity detection port.
|
|
3.6
|
Door Contact Module
|
Used for detecting the switch state of door, it can be connected with Sitemate AE, only takes up one switch quantity detection port.
|
|
3.7
|
Non-localized Leakage Detection
|
|
|
3.7.1
|
Non-Localized Line Leaking Collector
|
when the device has detected the leakage through ASC2100, it will output a relay signal through collector, it can be connected with Sitemate AE, and only takes up one switch quantity detection port.
|
|
3.7.2
|
Non-Localized Line Leaking Cable (10M)
|
It need to be allocated with Non-Localized Line Leaking Collector to detect whether the leaking has been happened, the cable length can be selected(no more than 30M), the price is calculated by meters.
|
|
3.8
|
Common Air Conditioning Monitor System
|
|
|
3.8.1
|
Air Conditioning Intelligent Remote Controller
|
it can remote control air conditioning switch state and can realize the remote restart function automatically.(one air conditioning needs one air conditioning intelligent remote controller), it needs to be allocated with Sitemate AE.
|
|
3.8.2
|
Photoelectric isolated conversion module
|
(one air conditioning needs one air conditioning intelligent remote controller and one photoelectric isolated conversion module), this module is used to change the RS485 signal to RS422 signal, it needs to be allocated with Sitemate AE
|
|
4
|
Localized Leakage Monitor System
|
|
|
4.1
|
Netmate II mini Leaking Monitor Host(internal)
|
One localized leaking detection modue needs to be allocated with one Netmate II mini leaking monitor host.(provide internal webpage, can be allocated with IPPower2009)
|
|
4.2
|
Localized Leaking Detection Module
|
can detect the precise leaking location through LDS-3100-02,then output through RS485 intelligent communication signal.
|
|
4.3
|
Localized Leaking cable(7.5M)
|
The length can be selected according to the real situation, it is mainly used to be allocated with localized leaking detection module to detect the leakage location.
|
|
4.4
|
Leaking Detection Module Outgoing Line
|
accessory
|
|
4.5
|
Leaking Terminal
|
accessory
|
|
4.6
|
Fixed glue stick
|
accessory
|
|
5
|
Precise Power Distribution Cabinet Monitor System
|
|
|
5.1
|
Netmate II mini Precise Power Distribution Cabinet Network Monitor Adapter
|
Used to monitor power distribution cabinet, collect the voltage, current, active power, reactive power and other data of power distribution.(One precise power distribution cabinet needs to be allocated with one Netmate II mini precise power distribution c
|
|
6
|
Common Power Distribution Cabinet Monitor System
|
|
|
6.1
|
Netmate II mini Intelligent Power Distribution Cabinet Network Monitor Adapter
|
Used to monitor power distribution cabinet, collect the voltage, current, active power, reactive power and other data of power distribution.(One common power distribution cabinet needs to be allocated with one Netmate II mini intelligent power distribution network monitor adapter)
|
|
6.2
|
Three Phase Intelligent Power Inspection
|
collect the voltage, current, active power, reactive power and other data of power distribution.(One common power distribution cabinet needs to be allocated with one three phase intelligent power inspection instrument)
|
|
7
|
Common Power Distribution Cabinet Output Core Branch Circuit State Monitor System
|
|
|
7.1
|
Sitemate Power Distribution Switch State Inspection Host
|
able to connect 2 D8H(Utility switch inspection module)at the same time, able to inspect 16 circuits switch state signal, it can be allocated with IPPower 2009.
|
|
7.2
|
Utility Switch Inspection Module
|
can detect 8 circuits utility switch signal at the same time, and output signal to Sitemate, it needs to take up 8 switch state signal detection terminal.
|
|
8
|
Precise Air Conditioning Monitor System
|
|
|
8.1
|
Netmate II mini Precise Air Conditioning Network Monitor Host(internal)
|
Monitor precise air conditioning data, need to be provided protocol and interface(One precise air conditioning needs to be allocated with one Netmate II mini precise air conditioning network monitor adapter)
|
|
9
|
Battery Monitor
|
|
|
9.1
|
One Battery Monitor(basic version, inspect battery voltage)
|
|
|
9.1.1
|
BatteryScan Battery Inspection Host
|
Real time monitor storage battery status, such as battery total voltage, monomer battery voltage, charge and discharge current, provide internal webpage, it can be allocated with IPPower 2009, and can support 10 module at most.
|
|
9.1.2
|
Battery Inspection Module Unit
|
Monitor 24 unit battery, (if the battery quantity is more than 24 , it needs to add a battery inspection module unit)this Module need to be allocated with battery inspection host and can be divided into 5 packs to detect at most.
|
|
9.1.3
|
Battery Clamp
|
|
|
9.1.4
|
Hall Sensor
|
accessory
|
|
9.2
|
One Battery Monitor(advanced version, inspect battery voltage and internal resistance )
|
|
|
9.2.1
|
Netmate II mini Battery Inspection Network Monitor Host(Internal)
|
Traffic industry
Shanxi Fenyang highway toll power environment wireless monitoring
South China fast line UPS centralized monitoring
Hangzhou round highway UPS centralized monitoring
Shenzhen-Foshan highway toll UPS centralized monitoring
Shenzhen-Shantou highway toll monitoring
Xiamen bus UPS centralized monitoring
Guangzhou white cloud airport computer room environment monitoring
Xiamen BRT computer room UPS network centralized monitoring
Yongtaiwen, Zhejiang province high-speed computer room UPS network centralized monitoring
Yangmao highway toll computer room power environment monitoring
China Easten Airlines computer room power environment SMS monitoring
Shantou-Fenyang highway computer room power environment monitoring
Communication industry
Liaoyang branch business hall computer room UPS wireless centralized monitoring
Beijing telecommunication business outlets computer room UPS centralized monitoring
Beijing Great Wall broadband CO., LTD outlets UPS centralized monitoring (NEW)
Shanghai Zhongjin SmarTone district broadband network computer room and server shutoff protection
Wuhan, Hubei province Changqing garden district wire TV broadband network
Part of Dongguan branch of China mobile base station computer room
Zhengjiang province branch of China Unicom mobile communication base station
Government industry
Nanchang Public Security Bureau(PSB)center computer room overall environment monitoring
Yinchuan Ningdong power supply bureau
Fuzhou Public Security Bureau(PSB)UPS centralized monitoring project
Beijing National Tax Bureau branchs UPS network monitoring and server shutoff protection
Shenyang statistics computer room power environment wireless monitoring
Yunnan Judicature bureau computer room power environment SMS monitoring
Fujian weather bureau computer room power environment monitoring
The Tibet autonomous region communication administration computer room power system SMS monitoring
Education industry
Tianjin Medical university computer room UPS monitoring
Tianjin university computer room UPS monitoring
Xi'an industrial university computer room power system network monitoring
Power industry
Hangzhou Central Electricity Authority computer room power system monitoring
Radio and Television industry
Qinhuangdao Radio and Television computer room power system environment monitor
Changzhou broadcast station computer room UPS network centralized monitor
Changzhou Radio and Television studio centre power system network monitor
Financial industry
Shenzhen development bank Beijing branch computer room monitoring
Zhengjiang Industrial and Commercial Bank of China computer room power environment monitoring
Zhengjiang Industrial and Commercial Bank of China outlets UPS centralized monitoring
Zhuhai branch of agricultural bank of China outlets power environment centralized monitoring
Shanghai securities company data center power system SMS monitoring
Nanjing branch of bank of communications outlets power system network centralized monitoring
Shanghai Industrial and Commercial outlets UPS network centralized monitoring
Xiamen rural credit cooperative outlets UPS network centralized monitoring
Shanghai China Minsheng Banking CO., Ltd outlets UPS network centralized monitoring
Xiamen branch of China Merchants Bank outlets UPS network centralized monitoring
Dalian branch of Shanghai Pudong Development Bank outlets UPS centralized management
Enterprise industry
Shenzhen foxconn company computer room and server shutoff protection
Beijing capital airport terminal airlines building computer room UPS centralized monitoring (NEW)
Haerbin Seismological bureau and Tonghe seismological station information center power environment monitoring
Shanghai East Jiasheng shipping company computer room power environment SMS monitoring
Guangzhou Watsons outlets UPS centralized monitoring
Service Hotline:400-6069-106 Copyright ©2009 Guangzhou Richcomm System Technologies Co.,Ltd
All rights reserved Richcomm
GZ ICP value-added telecom management license NO.05078802 |